Wiki

Version 14 (Niranjini Rajagopal, 01/28/2013 07:11 pm)

1 1 Anthony Rowe
h1. Building Energy Optimization
2 1 Anthony Rowe
3 2 Niranjini Rajagopal
h2. Project Description
4 2 Niranjini Rajagopal
5 2 Niranjini Rajagopal
The Building Energy Optimization System is a sensor network consisting of several power and environmental sensors to monitor and understand energy usage patterns with the objective of giving the user feedback on reducing the energy consumption.
6 2 Niranjini Rajagopal
7 2 Niranjini Rajagopal
h2. System Components
8 2 Niranjini Rajagopal
9 3 Niranjini Rajagopal
The network architecture is shown in the figure below.
10 3 Niranjini Rajagopal
11 6 Niranjini Rajagopal
!Energy_Sensor_Network4.jpg!
12 3 Niranjini Rajagopal
13 14 Niranjini Rajagopal
The Three-phase energy meter is used to measure the aggregate energy consumption of all appliances. Each plug-through power meter measures the energy of an individual appliance. Every electromagnetic-field based (EMF) energy sensor is placed in the proximity of an appliance, and detects the state change when the appliance turns on or off. The environmental sensors measure the ambient light, temperature, audio, pressure, acceleration and humidity and detect human motion in the proximity. The thermal scanner is mounted on the ceiling and generates a thermal map upon scanning the entire room. The thermal and the environmental sensors data can be correlated with the per-appliance energy consumption and can give useful information on usage patterns, and can also help detect building and appliance faults.
14 2 Niranjini Rajagopal
15 1 Anthony Rowe
Each of the sensors are described briefly below:
16 14 Niranjini Rajagopal
17 11 Niranjini Rajagopal
* *Environmental sensors*
18 10 Niranjini Rajagopal
19 9 Niranjini Rajagopal
The figure below shows the environment sensing board with all its sensors labeled.
20 1 Anthony Rowe
21 1 Anthony Rowe
!ff3-env-sensor.jpg!
22 1 Anthony Rowe
23 14 Niranjini Rajagopal
24 14 Niranjini Rajagopal
* *Thermal Scanner*
25 14 Niranjini Rajagopal
** Low-Cost Thermal Scanner
26 14 Niranjini Rajagopal
** Distributed Scanning
27 14 Niranjini Rajagopal
** 3D model construction
28 14 Niranjini Rajagopal
29 14 Niranjini Rajagopal
30 12 Niranjini Rajagopal
* *Three-phase energy meter*
31 13 Niranjini Rajagopal
** 3-Phase Circuit Panel Meter (110-240VAC)
32 13 Niranjini Rajagopal
** RMS Current, RMS Voltage, True Power, Apparent Power, Reactive Power, Power Factor
33 13 Niranjini Rajagopal
** 2KHz Output Rate
34 13 Niranjini Rajagopal
** 1W resolution with 20KW max load
35 13 Niranjini Rajagopal
** Local processing support asynchronous pushing of power events on change
36 1 Anthony Rowe
!3phase-meter.jpg! !3phase-bottom.jpg!
37 8 Niranjini Rajagopal
38 14 Niranjini Rajagopal
39 12 Niranjini Rajagopal
* *Plug-through energy meter*
40 9 Niranjini Rajagopal
** 1 outlet (110-240VAC)
41 9 Niranjini Rajagopal
** Mechanical relay switching
42 9 Niranjini Rajagopal
** RMS Current, RMS Voltage, True Power, Apparent Power, Reactive Power, Power Factor
43 9 Niranjini Rajagopal
** 2KHz Sampling Rate
44 9 Niranjini Rajagopal
** 1W resolution with 1700W max load
45 1 Anthony Rowe
** Local processing support asynchronous pushing of power events on change
46 9 Niranjini Rajagopal
!ff3-plug-front.jpg! !ff3-plug-back.jpg!
47 14 Niranjini Rajagopal
48 9 Niranjini Rajagopal
49 12 Niranjini Rajagopal
* *Magnetic-field based energy meter*